HSE has issued a safety notice after aninvestigation into a gasoline overfill of a carbon adsorption vapour recovery unit (VRU)

Having trouble viewing this email?View the content as a web page.

Health and Safety Executive logo

HSE ebulletin

Overfill of vapour recovery units

HSEs investigation into a gasoline overfill of a carbon adsorption VRU revealed concerns with its design.

The overfill prevention system was not independent of the basic process control system (BPCS), meaning that when the BPCS failed, the overfill prevention system also failed, resulting in a loss of containment.

This risked a significant fire and explosion, as well as extensive environmental damage.

Duty holders should follow a safe system of work to assess the risk of overfill, check equipment and where appropriate modify VRU control systems and/or implement independent control measures.